AC Power Corp.
Product Name:
AFC-33_Series_Three Phase
Description:
l
One key for
shutdown when fault.
l
Quick response
speed.
Response time
≤2ms.
l
High accurate
measurement for parameter:
²
Voltage, 0.15%FS+4COUNT;
²
Current, 0.2%FS+4COUNT;
²
Frequency, 0.1%;
²
Power, 0.3%FS+4COUNT.
l
Output voltage:
5~300V continuous adjustable.
Quick & convenient 3 scales of preset voltage for high and low voltage
simulation:
²
High: +10%~+25% of preset voltage;
²
Medium: preset voltage;
²
Low: -10%~-30% of preset voltage.
l
Pure output
sine-wave.
(Please see specification table).
l
Well protection
and fault alarm function: Input no-fuse breaker; electronic circuit instant trip for over voltage,
over current, over load, over temperature and short circuit protection and alarm
system.
l
Power module
design patent.
Specification:
Model
AFC-33006
AFC-33010
AFC-33015
AFC-33020
AFC-33030
AFC-33045
AFC-33060
AFC-33075
Capacity (kVA)
6
10
15
20
30
45
60
75
Circuit Type
IGBT/PWM type
Input
Phase
Three phase
Wave
Sine wave
Voltage
220V/380V
Voltage range
220V/380V±15%
Frequency range
50Hz±3Hz or 60Hz±3Hz
Power factor
0.9
Output
Phase
Three phase
Wave
Sine wave
Voltage
Low
5V~150V(L-N)
High
10V~300V(L-N)
Frequency
47~63Hz, 50Hz, 60Hz
Frequency regulation
≤0.01%
Max. current
High (A)
8.3
13.9
20.8
27.8
41.7
62.5
83.3
104.2
Low (A)
16.7
27.8
41.7
55.6
83.3
125.0
166.7
208.3
System
Power regulation
<1%
Load regulation
±1% (linear load)
Total harmonic distortion (THD)
2% (linear load)
Efficiency
≧90%
Response time
≦2ms
Wave factor
3:1
Protection device
Input no-fuse breaker, electronic circuit instant trip for over/low
voltage,
over current, over load, over temperature and short circuit protection
and alarm system
Indicator
Display
LED
Voltage
Show range: 0~600V, analytic degree: 0.1V,
Current
Show range: 0~700A, analytic degree: 0.01A(<100A)/0.1A(≥100A),
accurate degree: 0.2%FS+4COUNT
Power
Show range: 3kW~75kW, analytic degree: 0.01kW(<10kW)/0.1kW(≥10kW),
accurate degree: 0.3%FS+4COUNT
Frequency
Show range: 0~999.9Hz, analytic degree: 0.1Hz, accurate degree: 0.1%
Environment
Insulation resistance
DC500V
≥20MΩ
Withstand voltage insulation
AC 1800V 10mA/ 1Min
Cooling system
Fan cooling
Temperature
0℃~45℃
Humidity
0~90% (Non-condensing)
Altitude
≤1500m
Case No.
③
④
⑤
Weight(kg)
200
230
300
310
390
550
580
670
Remarks:①
Custom-made specifications are discussible;
②
All specifications are subject to change without prior notice.
accurate degree: 0.15%FS+4COUNT
This is the detailed information for AFC-33_Series_Three Phase, AFC 33 Series. The information includes model, name, description and specification for AFC-33_Series_Three Phase, AFC 33 Series. Related Keywords : AFC-33006 AFC-33010 AFC-33015 AFC-33020 AFC-33030 AFC-33045 AFC-33060 AFC-33075
Please send your Inquiries for AFC-33_Series_Three Phase, AFC 33 Series to us. We will contact you soon. Please also check out the related product categories below.