AC Power Corp.
Line Conditioner - 1~300KVA- APS Series (Microprocessor Controlled Type)
> APS-series
Product Name :
APS-series
Features & Advantages:
HIGH Input Power Factor, HIGH VA Efficiency, HIGH Over Load Capacity, HIGH Reliability.
◇5L :
LOW Environmental Pollution ( Green Energy ), LOW Electromagnetic Wave Interference,
LOW Audible Noise, LOW Maintenance Costs, LOW No Load Energy Consumption.
◇CLEAN :
Clean and constant AC Power output. No radiation interference to electromagnetic
field (EMF); No transmitting interference to electrified wire fence.
◇FAST :
Fast Response Time (≦4mS./step).
◇FLEXIBLE :
Any loads are applicable. Generator friendly.
◇NEW :
CE approval. New Design; New Circuits;
New Patent.
◇RELIABLE :
DSP/Microprocessor Control circuits increase the reliability and
stability.
◇SAFE :
Automatic Electronic Bypass Protection, Over Load Protection, Over
Range Protection to let your load well protected.
◇SAVE :
Superior No Load Energy Consumption reduces operating costs through utility
savings compared to SCR type or Ferroresonant Transformer. Compact size &
light weight saves your space and transportation fee.
◇STABLE :
Independent Phase Voltage Regulation. Characteristics will not be
violated under 100% unbalance load.
◇WIDE :
+/-25% input voltage range is useable.
Specification:
* Input & Output Voltage please refer to FORM
1
Model
APS-33010
APS-33015
APS-33022
APS-33030
APS-33045
APS-33060
APS-33075
Capacity
10kVA
15kVA
22kVA
30kVA
45kVA
60kVA
75kVA
Input(AC)
Phase
Three Phase
Voltage
208V/120V , 480V/277V
form
1
Voltage Range
± 18%
± 18% (25% Option)
Frequency
47Hz ~ 63Hz
Power Factor
0.95 ~ 1
Output(AC)
Phase
Three Phase
Voltage
208V/120V , 480V/277V
form
1
Frequency
Same as Input Frequency
Power Factor
± 0.7 ~ 1
VA Efficiency
≥ 98% Full Load / No Load energy
power consumption ≤ 0.2
Line Regulation
± 1% ~ ± 4%
± 1% ~ ± 2%
Load Regulation
± 1% ~ ± 4%
± 1% ~ ± 2%
Total Harmonic Distortion
< 1% (additional waveform
distortion
Response Time
≤ 4ms / Step
Indicator
Voltmeter
Show 0~300VAC for each phase
Ammeter
Show R.S.T. Load's Current
LED
Power abnormal , output voltage
overrun (high voltage / low voltage) , auto bypass supply
Protection
Over Range
Power Auto Shut & Led Indicator
Over Load
No Fuse Break
150% for 15Sec , 130% for 30Sec ,
110% for 300Sec
Auto Bypass
Led Indicator & Alarm
Noise Suppressors
High energy surge absorber 、LC
Filter、EMI Filter (option)
R.S.T. Phase Failure
Led Indicator (option) &
Alarm (option) & Auto shut off (option)
Overload Capacity
200% for 10 seconds ; 500%
for 50ms
Audible Noise
≤ 50dB
≤ 55dB
Cooling System
Natural cooling
Fan cooling
Connections
Terminal
Environment
Ambient
0ºC ~ 40ºC
Humidity
0~95% (Non-condensing)
Model
APS-33100
APS-33120
APS-33150
APS-331800
APS-33240
APS-3300
Capacity
100kVA
120kVA
150kVA
180kVA
240kVA
300kVA
Input(AC)
Phase
Three Phase
Voltage
208V/120V , 480V/277V
form
1
Voltage Range
± 18% (25% Option)
Frequency
47Hz ~ 63Hz
Power Factor
0.95 ~ 1
Output(AC)
Phase
Three Phase
Voltage
208V/120V , 480V/277V
form
1
Frequency
Same as Input Frequency
Power Factor
± 0.7 ~ 1
VA Efficiency
≥ 98% Full Load / No Load energy
power consumption ≤ 0.2
Line Regulation
± 1% ~ ± 2%
Load Regulation
± 1% ~ ± 2%
Total Harmonic Distortion
< 1% (additional waveform
distortion
Response Time
≤ 4ms / Step
Indicator
LCD
Display electrical parameters .
stat of the control , memories of history events
LED
Power abnormal , output voltage
overrun (high voltage / low voltage) , auto bypass supply
Protection
Over Range
Power Auto Shut off (option) & Led Indicator
Over Load
150% for 15Sec , 130% for 30Sec ,
110% for 300Sec
Auto Bypass
Led Indicator & Alarm
Noise Suppressors
High energy surge absorber 、LC
Filter、EMI Filter (option)
R.S.T. Phase Failure
Led Indicator (option) &
Alarm (option)
Overload Capacity
200% for 10 seconds ; 500%
for 50ms
Audible Noise
< 45dB
Cooling System
Air force Fan
Connections
Terminal
Copper Busbar
Environment
Ambient
0ºC ~ 40ºC
Humidity
0~95% (Non-condensing)
1. Other Input Ranges are on request.
2. Custom-made specifications are on request.
3. All specifications are subject to change without prior notice.
4.Catalogue Download
This is the detailed information for APS-series, APS-33 series. The information includes model, name, description and specification for APS-series, APS-33 series. Related Keywords : AC,Automatic,AVR,Changed,Conditioner,Controlled,Converter,Corp,DC,Frequency,Ground,Inductive,Line,Manufacturer,Microprocessor,Military,Online,Phase,Power,Programmable,Regulator,SCR,Shore,Source,Stabilizer,Supply,Taiwan,Tap,Three,Units,UPS,Variable,Voltage
Line Conditioner - 1~300KVA- APS Series (Microprocessor Controlled Type)
> (APS-11 series) APS-seriesPlease send your Inquiries for APS-series, APS-33 series to us. We will contact you soon. Please also check out the related product categories below.