Introduction of Inductive Voltage Regulator - APH Series
Currently ,as the economy grows very fast , the electricity consuming raises
up and the
shortage of power supply happens much often. The fuel crisis , energy crisis ,
and environment
pollution come along with it . Human societies are facing more and more electric
problems and
difficulties. AS for an enterprise , power problems always come as first
concern.
In case your device is under the conditions or impacts of over power
consuming , large eq-
uipments , or electric power problem such as voltage fluctuation / spikes /
surge / noise , it will
result in device abnormality, short device lifetime, part damage, or even
function failure.
Our inductive Voltage Regulator - APH series is designed for solving these
problems, and
offering the stable, safe, and clear power. With the innovative technology,
creative, and continues
development and research, we offer you the latest generation of Inductive
Voltage Regulator -
APH Series , which is very popular among our world wide customers.
Electric Feature
STRONG DURABLE & High RELIABILITY
No Contact Point. Capable to sustain Spike , Surge or Impulse lash coming for
Non-linear load .
Low Faulty Rate. Long Equipment Life.
PROTECTION:
Redundant Circuit Control
Event History Inside Memory for up to 200 events
Loss Phase, Phase Reversed Protection
Output Over Voltage & Under Voltage Protection
Output Overload Protection
HIGH OVERLOAD CAPABILITY:
100% continuous load; 200% transient current to 5 minutes;
NEW USER INTERFACE:
LCD; Blue Backlight; White Words
RS-485 communication port
Push buttons with light convenient to operate under dark
Remote signal, measurement, and control functions to monitor and control your
equipments
1500KVA MAX. CAPACITY PER UNIT; HIGH VOLTAGE POWER
SOURCE:
Inductive type Voltage Regulator is the unique capable to fabricate 1500 KVA max
per one unit
Specification:
This is the detailed information for APH-Series, APH-Series. The information includes model, name, description and specification for APH-Series, APH-Series. Related Keywords : APH-330100
APH-330150
APH-330200
APH-330300
APH-330400
APH-330500
APH-330600
APH-330800
APH-331000
APH-331250
APH-331500
Model
APH-330100
APH-330150
APH-330200
APH-330300
APH-330400
Capacity
100kVA
150kVA
200kVA
300kVA
400kVA
Circuit Type
Inductive Voltage Regulator
Input (AC)
Phase
3Φ3W / 3Φ4W
Voltage Range
Voltage ± 15% (Option ± 10% ~ ±30%)
Frequency
47Hz ~ 63Hz
Output(AC)
Phase
3Φ3W / 3Φ4W
Voltage
190V / 200V 208V , 220V / 230V / 240V ,
380V / 400V / 415V
Accuracy
± 1.5% (±1%~±5% Adjustable)
Voltage Modulation
≤ 4 V/S
Overload
125%-40min,150%-20min,175%-10min,200%-5min
Total Harmonic Distortion
≤ 1% (VA Efficiency)
VA Efficiency
≥ 97%
Measurement
Input Line Voltage and Frequency; Output Line Voltage, Phase Voltage,
Line Current, and Frequency;
VA, W, P.F.; Load Rate; Internal Temperature
Protection
Loss Phase, Phase Reversed Protection
Output Over Voltage & Under Voltage Protection
Output Overload Protection
Over Temperature
Redundant Circuit Control
Event History -Inside Memory for up to 200 events
User Interface
Operation
LCD and Indication
Alarm
AlarmⅠ(Audio)、Alarm Ⅱ(Activate)
Communication
RS-485
Software
Remote Control and Monitor
Environment
Working Temperature
-5ºC
~ 40ºC
Storage Temperature
-30ºC
~ 70ºC
Humidity
< 95%
Altitude
< 1000 meter
Cooling System
Fan cooling
Others
Noise
≤ 60dB
Optional
Auto transformer
Full time lightning and surge protection
Remote Control for
the Power on & off of the output (100~400kVA Models)
Model
APH-330500
APH-330600
APH-330800
APH-331000
APH-331250
APH-331500
Capacity
500kVA
600kVA
800kVA
1000kVA
1250kVA
1500kVA
Circuit Type
Inductive Voltage Regulator
Input (AC)
Phase
3Φ3W / 3Φ4W
Voltage Range
Voltage ± 15% (Option ± 10% ~ ±30%)
Frequency
47Hz ~ 63Hz
Output(AC)
Phase
3Φ3W / 3Φ4W
Voltage
190V / 200V 208V , 220V / 230V / 240V ,
380V / 400V / 415V
Accuracy
± 1.5% (±1%~±5% Adjustable)
Voltage Modulation
≤ 4 V/S
Overload
125%-40min,150%-20min,175%-10min,200%-5min
Total Harmonic Distortion
≤ 1% (VA Efficiency)
VA Efficiency
≥ 97%
Measurement
Input Line Voltage and Frequency; Output Line Voltage, Phase Voltage,
Line Current, and Frequency;
VA, W, P.F.; Load Rate; Internal Temperature
Protection
Loss Phase, Phase Reversed Protection
Output Over Voltage & Under Voltage Protection
Output Overload Protection
Over Temperature
Redundant Circuit Control
Event History -Inside Memory for up to 200 events
User Interface
Operation
LCD and Indication
Alarm
AlarmⅠ(Audio)、Alarm Ⅱ(Activate)
Communication
RS-485
Software
Remote Control and Monitor
Environment
Working Temperature
-5ºC
~ 40ºC
Storage Temperature
-30ºC
~ 70ºC
Humidity
< 95%
Altitude
< 1000 meter
Cooling System
Fan cooling
Others
Noise
≤ 60dB
Optional
Auto transformer
Full time lightning and surge protection
Remote Control for
the Power on & off of the output (100~400kVA Models)
1. Other Input Ranges are on request
2. Custom-made specifications are on request
3. All specifications are subject to change without notice
4.
Catalogue Download
Please send your Inquiries for APH-Series, APH-Series to us. We will contact you soon. Please also check out the related product categories below.