AC Power Corp.
Product Name:
APU Three phase series
Description:
1. Double Conversion - True On-Line UPS with zero transfer time.
2. INDUSTRIAL grade UPS.
3. IGBT / PWM technology for high efficiency & high reliability. Small size and
low noise.
4. Microprocessor Control with fast and precise response.
Safe
1. Battery Maintenance Bypass Breaker.
2. Independent tree phase inverter , able to support 100% unbalance loading.
3. Isolated Rectifier & Battery Charger, Load's current won't be affected when
input power returns.
4. EMI/DFI and over voltage protection.
5. Bidirectional static switch.
6. Overload & short circuit protection.
7. With output and input isolation transformer in order to prevent noise and
lightening & suit for SMT/AI/BGA precision equipment.
8. Static bypass and maintenance bypass are standard features, allowing the UPS
to maintenance power even during high overloads of mantenance.
Flexibility
1. 12 pulse rectifier optino.
2. Expandable battery (option).
3. RS-232 communication port and SNMP management are available on request.
Easy
1. Modular design. Easy maintenance & service
2. Intelligent LED & LCD Display for operation guide & UPS status
3. Compact size.Easy to move & space-saving.
Specification:
Model
APU-33010
APU-33015
APU-33020
APU-33030
APU-33045
APU-33060
APU-33075
APU-33100
Capacity
10kVA
15kVA
20kVA
30kVA
45kVA
60kVA
75kVA
100kVA
Input (AC)
Phase
Tree phase
Voltage
220V / 380V ± 10% (T)
form 1.
Frequency Range
50Hz ± 0.3Hz or 60Hz ± 3Hz
Power Factory
0.8
Output(AC)
Phase
Tree phase
Rated voltage
220V / 380V ± 10% (T)
form 1.
Voltage adjusted Range
< ± 5%
Frequency
55Hz ± 0.3Hz or 60Hz ± 3Hz
Power Factory
0.8
Static Regulation
± 1% (At line load)
Dynamic Regulation
± 4% (load rang : 0~100%)
System Efficiency (AC→AC)
> 87% (Full load)
Wave
Pure Sine Wave
THD
(Total harmonic distortion)≤ 3% (At line load)
Crest Factor
3 : 1
Battery
Type
Sealed lead acid , maintenance free battery
Voltage
192Vdc
240Vdc
Size
12V/17Ah
12V/26Ah
12V/40Ah
12V/65Ah
12V/100Ah
12V/100Ah
12V/100Ah
12V/100Ah
Quantity
16
20
Backup Time (Standard type)
10-15min (Full load)
Recharging time
The battery recharge to 90% for 10hr after
discharge completely
Transfer Time
AC line ↔Battery Mode
0ms
AC line ↔Bypass Mode
< 2ms (Full load)
Indicator
LCD
UPS working status , line
mode , battery mode , bypass mode ,overload
Overload Capacity
100% work continuously
125% for 10min , then transfer to bypass mode
150% for 30s , then transfer to bypass mode
Audible Alarm
Low voltage , over temperature , bypass ,
abnormal AC line , overload , over voltage
Audible Noise (1 meter)
< 65dB
Communication Interface
RS-232 (Optional)
Cooling System
Fan cooling
Environment
Ambient Temperature
0ºC
~ 40ºC
Humidity
0 ~ 95% (Non- condensing)
Altitude
0m ~ 1500m
Size (mm)
W x H x DUPS
700x430x1330
800x600x1600
1000x800x1800
Battery
460x480x1330
420x600x1600
600x800x1800
600x800x1800 *3
Weight (kg)
UPS
263
315
330
447
629
777
869
1900
Battery
161
218
298
391
450
671
671
1342
1. As to the required voltage , please refer to
form 1.
2. weight and size vary with input and output voltage , please contact us.
3. The backup time according to customer demand , please contact us.
4. All specifications are subject to change without notice.
5. Catalogue Download
This is the detailed information for APU Three phase series, APU-33_series. The information includes model, name, description and specification for APU Three phase series, APU-33_series. Related Keywords : APU-33010 APU-33015 APU-33020 APU-33030 APU-33045 APU-33060 APU-33075 APU-33100
Please send your Inquiries for APU Three phase series, APU-33_series to us. We will contact you soon. Please also check out the related product categories below.