AC Power Corp.
Product Name:
AEU-33 Series
Description:
Super Wide Input Frequency Window Benefits: AEU11 Series (1 / 2 / 3 / 6 / 10kVA ) UPS
AEU31 Series (10 / 15 / 30kVA ) UPS
AEU33 Series (20 / 30 / 40 / 60kVA ) UPS
Online Operation when Input Phase Fail Self-diagnosis Auto-switch between Boost and Float Recharging Temperature Compensation Module-designed DC Charge (for AEU11 / AEU31 ) ■We are authorized
distributor of Emerson Hipulse 7000 series (80kVA , 120kVA,160kVA
Super Wide Input Voltage Window
When one phase fails , can operate in on-line mode load equal to 50% of
the rating capacity.
When two phase fails , can operate in on-line mode load equal to 25% of the
rating capacity.
Intelligent Battery
Management
Auto-adaptable on EOD (End of Discharge) Adjustment
and automatically adjust the EOD for best performance of the battery . In
this way , over-discharge of
battery is avoided.
200kVA , 300kVA, 400kVA,500kVA,600kVA,800kVA) with the special features of three
phases input and tree phase output (380/400/415Vac) and parallel system which
can extend
to 6 units with/without MSS.
Specification:
Model
AEU-33020L
AEU-33030L
AEU-33040L
AEU-33060L
Capacity
20kVA
30kVA
40kVA
60kVA
Rectifier
Input (AC)Phase
Three-phase , three-line
Voltage
380V/400V/415V (Linear to line voltage)
Voltage Range
-45% ~ ±15%
Harmonic current distortion
< 3%
Frequency Range
50 Hz ± 10%
Power Factory
> 0.99
Bypass
Input(AC)Voltage
380V (Line to line)
Voltage Range
± 10%
Phase
Three-phase , four-line
Frequency Range
50 Hz ± 10%
Output(AC)
Voltage Regulation
± 1%
Dynamic Voltage Transient Response
± 5% (0% ~ 100%)
Dynamic Transient Response Time
0
Voltage Distortion (Linear laod)
THD < 1% (Line to nature voltage)
Voltage Distortion (NonLinear laod)
THD < 3% (Line to nature voltage)
Power Factory
0.8 (Lagged)
Frequency Sync. Range
50Hz ± 2Hz (Adjust every 0.25Hz)
Frequency Regulation (Battery mode)
0.02%
Phase Displacement (tree phase)
120 ± 0.5
º (Balanced load or unbalanced load)
Voltage Unbalance Rate at 100% Unbalanced Load
< 1%
Frequency Slew Rate
< 1Hz/s
Overload Capacity (Inverter)
105% ~ 125% for 10min ± 0.1min ; then transfer to
bypass mode ;
125% ~ 150% for 1 min ; then transfer to bypass mode ;
Overload Capacity (Bypass)
< 135% rated current continuously ;
135~170% for 1 min ; > 170% for 1s
Ratio of Output Current Peak value to RMS value
3 : 1
Transfer Time
0
Syetem
System Efficiency
Up to 92% ( On battery mode , can reach
96%)
Indicator
LCD + LED
EMC/EMI
Conduction
EN50091-2
Radiation
EN50091-2 CLASS A
Harmonic
IEC1000-3-4
Anti-jamming
EN61000-4-2,3,4,6,8,9,11 Level III ;
EN61000-4-5 Level IV
Safety Standard
CCEE (EN60950)
Audible Noise (1m)
< 55dB (1m)
Cross Current without Load
< 1A
Current Unbalance Rate (1+1)
< 1%
Insulation resistance
> 2M (500Vdc)
Insulation Strength
(Input to ground , output to ground)
2820Vdc, leakage current < 3.5mA , 1min without arc
Surge Protection
Satisfy the class IV requirements
specified by IEC60664-1 , that is the ability to withstand 1.2/50μs
+ 8/20μs no lower than 6kV/3kA
Protection Index
IP21
Size (mm) W x H x D
600x1400x860
800x1800x860
Weight (kg)
440
528
654
811
1. Additional features and options available, please contact our sales representative.
2. One year warranty.
3. All specifications are subject to change without notice.
4. Catalogue Download
This is the detailed information for AEU-33 Series, AEU-33 Series. The information includes model, name, description and specification for AEU-33 Series, AEU-33 Series. Related Keywords : AEU-33020L AEU-33030L AEU-33040L AEU-33060L
Please send your Inquiries for AEU-33 Series, AEU-33 Series to us. We will contact you soon. Please also check out the related product categories below.