AC Power Corp.
Product Name:
AEU-31 Series
Description:
Super Wide Input Frequency Window Benefits: AEU11 Series (1 / 2 / 3 / 6 / 10kVA ) UPS
AEU31 Series (10 / 15 / 30kVA ) UPS
AEU33 Series (20 / 30 / 40 / 60kVA ) UPS
Online Operation when Input Phase Fail Self-diagnosis Auto-switch between Boost and Float Recharging Temperature Compensation Module-designed DC Charge (for AEU11 / AEU31 ) ■We are authorized
distributor of Emerson Hipulse 7000 series (80kVA , 120kVA,160kVA
Super Wide Input Voltage Window
When one phase fails , can operate in on-line mode load equal to 50% of
the rating capacity.
When two phase fails , can operate in on-line mode load equal to 25% of the
rating capacity.
Intelligent Battery
Management
Auto-adaptable on EOD (End of Discharge) Adjustment
and automatically adjust the EOD for best performance of the battery . In
this way , over-discharge of
battery is avoided.
200kVA , 300kVA, 400kVA,500kVA,600kVA,800kVA) with the special features of three
phases input and tree phase output (380/400/415Vac) and parallel system which
can extend
to 6 units with/without MSS.
Specification:
Model
AEU-31010L
AEU-31015L
AEU-31020L
Capacity
10kVA
15kVA
20kVA
Input (AC)
Phase
Three-phase , four-line
Voltage
380Vac (Line to line)
Voltage Range
If the Phase voltage is in the range of 176
~276Vac , UPS can work normally with full load
If the Phase voltage is in the range of 120 ~176Vac ,the ability of UPS to
supply the load will decrease linearly with decreasing of input voltage
. It can work with half load when the voltage is 120Vac
Working Under Phase Failure condition
If one phase fails , the other two phases
in the range of
176 ~ 276Vac ,UPS can work with 50% rate load.
If one of the other two phases in the range of 120~176Vac , UPS ability
to supply the load will decrease linearly. When the voltage is 120Vac ,
UPS can work with 25% load
If two phase fails , the other phase in the range of 176~276Vac ,UPS can
work with 25% rate load .If the one voltage in the range of 120~176Vac ,
UPS ability to supply the load will decrease linearly. When the voltage
is 120Vac , UPS can work with 12.5% load
Frequency Range
45 ~ 55 Hz
Power Factory
0.99
Output(AC)
Power Factory
Standard 0.7 (Can reach 0.8 )
Voltage
220Vac ± 1%
THD(Total harmonic distortion)
< 3% (at linear load)
< 5% (at no linear load)
Inverter Overload Capacity (Power or battery)
105% ~ 125% for 10min ; then transfer to
bypass mode ;
125% ~ 150% for 1 min ; then transfer to bypass mode ;
> 150% for 200ms;then transfer to bypass mode ;
Crest Factor
3 : 1
Bypass Voltage
120 ~ 253Vac
System Efficiency
Up to 92% (On battery mode , can reach 96%)
Transfer Time
0
Audible Noise
< 55dB (1m)
< 60dB (2m)
Indicator
LED + LCD
(Chinese and English display selectable)
Safety Standard
CCEE (EN60950)
Bearable Maximum Input Voltage
Line voltage 554Vac , 1Hour (Static)
EMI Standard
Conduction : EN55022 Class A
Radiation: EN55022 Class A
Interference Standard
EN61000-4-2,3,4,6,8,11 Level III ;
EN61000-4-5 Level IV
MTBF (System)
300,000 hr
MTTR (Board maintenance)
1Hr
Insulation resistance
> 2M (500Vdc)
Insulation Strength
(Output to ground , input to ground)
2820Vdc , leakage current < 3.5mA
Surge Protection
IEC60664-1-IV
Size (mm) W x H x D
280 x 875 x 770
Weight (kg)
97
116
Redundancy Technology
Hot backup through series connection (6K ,
10K)
1. Additional features and options available, please contact our sales representative.
2. One year warranty.
3. All specifications are subject to change without notice.